Nothing Was Running
Shortly after 6 pm on 10 November, a chemicals plant on the Texas Gulf Coast reported a chemical odor inside its own fence. The product was unidentified at first, as it usually is. At 6:50 pm the city of Deer Park put a shelter-in-place order in effect; it was lifted at 10 pm. A neighboring chemicals site sheltered its staff as a precaution. A fire was extinguished, the operator reported no injuries, and fence-line monitoring found nothing unusual.
The chemistry is the part to read twice. The unit was idle, under maintenance. Hydrogen sulfide did not come from a storage vessel or a line in service; it was manufactured on site when a solid, phosphorus pentasulfide, met water. Responders were not isolating an inventory; they were managing a reaction rate, set by how much water reached the solid.
The Residue Is a Reagent
Phosphorus pentasulfide hydrolyses in a ratio that matters to anyone specifying equipment: each portion that gets wet yields both hydrogen sulfide and phosphoric acid. Two hazards, one puddle, and the acid is what remains on a glove or a boot after the gas has dispersed.
That inverts the usual assumption about contamination. Dust on a gauntlet, in a boot lug or along a stitched seam is not a dose to be sampled once and written off. It is a small reactor with its own fuel. Sweat inside a glove or a damp sock restarts the hydrolysis at skin level, under a barrier that then holds gas against the body.
Recovery from a water-reactive solid is dry. Brush it, vacuum it with HEPA filtration, keep it away from water until it is bagged. The reflex that makes most decontamination work safe, wetting everything down, is the reflex that switches this material back on.
Decon Water Is a Feed Line
Most decontamination lines treat water as the cleaner and runoff as the waste. Here water is also a reactant, so the two streams separate before anyone steps out of a suit.
Position matters. Hydrogen sulfide is heavier than air, so the worst air in a work area sits at ankle height: where the boots are standing, and where a monitor on a chest harness never samples. This one reached a residential district, so the readings that mattered were at ground level and at the boundary.
Footwear should be specified twice, for dry recovery and for wet decontamination. Dry: a smooth shaft with no laces or stitched channels that trap powder, a sole bond that survives acid, and a removal method that keeps hands off the outer surface. Wet: a marked change point where kit is bagged, labeled, and opened outdoors or under extraction. A sealed bag of wet contaminated equipment will generate gas.
Hand protection carries the acid, not the gas. Supplied air deals with the gas; the glove's job is degradation resistance, seam integrity and a cuff that overlaps the sleeve.
What Belongs in the Maintenance Package
Four questions strip most of this exposure out of an idled-unit job.
Ask for the water-reactive inventory by unit, not by process. Solids harmless dry and hazardous wet are rarely listed beside the toxic gases, so two different people read two lists.
Ask for a water-free cleaning procedure for equipment coming out of service, and for a named person to authorize any jet-washing.
Ask where the monitors sit: the low point of the work area, the bagging station, the boundary where boots come off.
Ask what the decon runoff is, since it will carry a pH and a sulfide load rather than water, and who supplies boots to the contract crew that does not work for you.